Hahn & Sohn C70NG petrol generator
Hahn & Sohn C70NG is a three-phase soundproofed natural gas generator with an output of 62.5 kVA (50 kW) in continuous operation and 68.75 kVA (55 kW) in standby operation. It is powered by a four-cylinder Cummins 4BTAA3.9-G58 engine, electricity is generated by a Stamford alternator, and operation is controlled by a ComAp InteliLite 4 AMF25 controller. The sound-insulated enclosure keeps the noise level at 74 dB at a distance of 7 m.
C70NG is a natural gas generator for locations where natural gas is available and three-phase 400 V / 50 Hz power of up to 68.75 kVA is required. The Cummins 4BTAA3.9-G58 engine has 4 cylinders and a displacement of 3.9 l, is turbocharged with charge air cooling (air-to-air). Rated speed is 1,500 rpm and engine speed is controlled by the engine control unit (ECU).
- The electrical section consists of a single-bearing Stamford S1L2-Y1/50KW alternator with brushless self-excitation, IP 23 protection, class H insulation, and voltage regulation accuracy of ±0.5%. The alternator has 12 leads.
- Control is provided by the ComAp InteliLite 4 AMF25 with a 7-digit display, integrated speed governor and AVR. The controller monitors generator output (kW, kVA), protects against overload, monitors start failure, and enables emergency shutdown.
- The gas section of the engine compartment contains a gas line with valve, pressure gauge, and gas detector with a digital display. The inside of the enclosure is lined with sound-absorbing material, the doors are secured with locks, and the engine compartment is accessible from both sides.
- Gas consumption at continuous output: 19 m³/h at 100%, 15 m³/h at 75%, 10 m³/h at 50%, and 5 m³/h at 25% load.
- Directly on the machine are four industrial three-phase sockets mounted on a common rail and labelled L1-L4. The switchboard contains a main four-pole CHINT 100 A circuit breaker with leakage current protection and a set of circuit breakers for the individual outputs. The control panel is located behind a transparent window, and the enclosure is fitted with an emergency stop button. The base frame has forklift pockets.

Why customers choose it
- Natural gas operation - runs on natural gas from a fixed supply, with no need to refill diesel or petrol.
- Cummins engine and Stamford alternator - branded components.
- Three-phase 400 V output with 62.5 kVA (prime) / 68.75 kVA (standby) output - suitable for commercial premises, construction sites, and backup power.
- Sound-insulated enclosure - 74 dB at 7 m.
- ComAp AMF25 controller with display and protection functions.
- Gas detector in the engine compartment.
- Industrial sockets directly on the machine and a circuit breaker with leakage current protection
- 12-month or 1,000 operating-hour warranty on both the engine and alternator (whichever occurs first).
Practical tip
When planning the installation, allow for a weight of 1,196 kg and dimensions of 2,500 x 1,050 x 1,500 mm. Connection to the gas supply and exhaust system should be carried out by an authorised specialist company.
Key features
- Output 62.5 kVA / 50 kW (prime), 68.75 kVA / 55 kW (standby)
- Fuel: natural gas
- Voltage 400 V, 50 Hz, three-phase, rated current 89 A
- Cummins 4BTAA3.9-G58 engine, 4 cylinders, 3.9 l, turbocharged with charge air cooling
- Stamford S1L2-Y1/50KW alternator, IP 23, class H insulation, AVR ±0.5%
- ComAp InteliLite 4 AMF25 controller, 7-digit display
- Noise level 74 dB at 7 m
- Gas detector and gas line with valve and pressure gauge
- 100 A main circuit breaker, four sockets on the machine, emergency stop button
- Warranty 12 months / 1,000 hours
Use / Installation / Operation
- Designed for operation with a natural gas supply.
- The machine is supplied as one complete unit on a frame designed for forklift handling.
- Installation of the gas supply, exhaust system, and connection to the electrical mains must be carried out by an authorised specialist company.
- The installation, operating, and maintenance manual (safety instructions, installation, handling, commissioning, battery maintenance) is available for download from the product page.
- Fluid capacities: engine oil 16.4 l, coolant (engine only) 10 l.
Additional parameters
| Category: | Backup generators |
|---|---|
| Warranty: | 1 yaer |
| Weight: | 1201 kg |
| Model: | C70NG |
| Fuel: | natural gas |
| Rated power: | 62,5 kVA / 50 kW |
| Standby power: | 68,75 kVA / 55 kW |
| Voltage: | 400 V (combined), 50 Hz, 3-phase |
| Rated current: | 89 A |
| Power factor: | 0,8 |
| Noise level: | 74 dB @ 7 m |
| Engine: | Cummins 4BTAA3.9-G58 |
| Engine specification: | 4-stroke, water-cooled, in-line, 4-cylinder, direct injection, turbocharged with intercooling (air-to-air) |
| Engine capacity: | 3,9 l |
| Bore x stroke: | 102 x 120 mm |
| Compression ratio: | 10,5:1 |
| Revolutions per minute: | 1,500 rpm (idling 750–850) |
| Speed control: | ECU |
| Ignition sequence: | 1-3-4-2 |
| Starter motor: | 24 V |
| Gas consumption (prime): | 19 / 15 / 10 / 5 m³/h at 100 / 75 / 50 / 25 per cent |
| Oil capacity: | 16,4 l |
| Coolant (engine only): | 10 l |
| Maximum oil temperature: | 121 °C |
| Max. coolant temperature (standby / prime): | 104 / 100 °C |
| Max. exhaust back pressure: | 10 kPa |
| Alternator: | Stamford S1L2-Y1/50kW, single bearing, IP 23, H-class insulation, brushless |
| Voltage regulation accuracy: | ±0.5 per cent |
| Control unit: | ComAp InteliLite 4 AMF25 |
| Dimensions (L x W x H): | 2 500 x 1 050 x 1 500 mm |
Product rating
Be the first who will post an article to this item!
Discussion
Be the first who will post an article to this item!